External Pressure Coefficients for Wall Loads (Bug 2595)

Starting with version 8.11 of the program, instead of the expressions for external pressure coefficient, Cp, based on height to depth ratio from NBC 2010 Figure I-15 , the program always used the value of 0.27 in the range 0.25 < H/D < 1.0, resulting in loading that was less than half of what it should be. This has been corrected and the program uses 0.27( H/D + 2.0) for windward walls and -0.27( H/D + 0.88) for leeward walls.

Note that for buildings in these ranges are ordinarily designed using the low-rise method, I-7, but Shearwalls does not use this method for multi-block structures, and it is likely not be used for flat roofs, so this problem is likely to have occurred for these types of structures.