Sizer implements earthquake load combinations according to the following design code references.
NBC
NBC Structural Commentaries
CSA O86-14
The table below gives the load combinations that include E along with load types D, L, Ls, S and W, and a comparison between the old and new design codes in this regard. Refer to the comments at the end of this section to extend this for load combinations with Ds, Lt or H loads.
Note that in this table, we do not list all the sub-combinations of combinations – if the combination says “plus D, S, W”, then one would go to the ultimate limit states table and see that D + S; D+ W, and D are also generated.
Load Type |
Combination |
|
|
D, E |
1.0D + 1.0E plus D only |
D, E, L |
1.0D + 1.0E + 0.5L plus D,E; D,L |
D, E, S |
1.0D + 1.0E + 0.25S plus D,E; D,S |
D, E, W |
D,E and D,W |
D, E, L, S interior surface |
1.0D + 1.0E + 0.5L + 0.25S plus D,E; D,L,S; |
D, E, L, S exterior surface |
1.0D + 1.0E + 0.5L 1.0D + 1.0E + 0.25S plus D,E; D,L; D,S |
D, E, L,W |
D,E,L and D,W,L |
D, E, S,W |
D,E,S and D,W,S |
D, E, S,W,L |
D, E, L, S and D,W,L,S |
D, E, Ls |
1.0D + 1.0E + 1.0Ls plus D,E; D,Ls |
D, E, Ls, L |
1.0D + 1.0E + 1.0Ls + 0.5L plus D,E; D,Ls,L; D,Ls, D,L3 |
D, E, Ls, S interior |
1.0D + 1.0E + 1.0Ls + 0.25S plus D,E; D,Ls,S; D,Ls; D,S3 |
D, E, Ls, S exterior |
1.0D + 1.0E + 1.0Ls 10D + 1.0E + 0.25S plus D,E; D,Ls; D,S3 |
D, E, Ls, L,S interior |
1.0D + 1.0E + 1.0Ls + 0.25S + 0.5L plus D,E; D,L, Ls,S and its subtypes |
D, E, Ls, L,S |
1.0D + 1.0E + 1.0Ls 1.0D + 1.0E + 0.25S plus D,E; D,L,Ls,S and subtypes |
3D, L or D,S not strictly necessary but created for technical reasons
4Design code refers to storage “occupancies”, indicating that all live loads are increased to 1.0
Earthquake and Wind Loads
When E, Ls and W are on the same member, the combinations containing Ls and W, but not E are not listed. Refer to the tables in Live Storage Load Combinations for these combinations.
Liquids in Tanks Loads Lt
The combinations containing Lt can be derived by replacing L by L + Lt.
Hydrostatic Loads
Adding H arrives at the load combinations for hydrostatic loads H to each of these combinations, while also retaining the combinations without H.
Dead loads due to soil
The dead load due to soil factor of 1.25 does not apply to earthquake load combinations. However, entry of the Ds load is still possible with earthquakes to examine the non-E combinations. Therefore the program will continue to make Ds part of the E combinations. These combinations are arrived at by replacing D with D + Ds in this table, without repeating the load combinations for D only.
Dead-load-resisting-failure load combinations
Notes 2 and 3 of NBC Commentaries Table A-3, indicate that 1.0 is to be used as the stress reversal factor for Dead loads combined with Earthquake, and neither the CSA O86 or NBC include a 0.9 factor for earthquake load combinations, therefore SIzer does not include dead-load-resisting-failure combinations for earthquake loading.
Serviceability load combinations
Neither the NBC nor the CSA O86 includes earthquake serviceability factors. The NBC structural commentaries, tables A4 and A5, do include earthquake load combinations for tables for damage to components and short term structural deflection, but further commentaries discuss lateral deflection (storey drift), and do not consider deflection of bending members.
Therefore, and there are no serviceability load combinations for Earthquake loads in Sizer, and none of the combinations containing E in the above table will be checked for deflection.
Patterns
Earthquake loads are not patterned, and live and snow loads are not patterned in earthquake combinations.
The load types referred to here are D=dead W=wind S=snow H=earth,groundwater E=earthquake L=live(use,occupancy) Ls=live(storage,equipment) Lt =live(liquids in tanks) Ds=dead load due to soil.