Previous Topic

Next Topic

Book Contents

Book Index

Minimum Wind Loads

Important Note – These are descriptions to changes implemented in WoodWorks Shearwalls for version 10.0 and may not reflect current behavior

The program has implemented the change in intensity for minimum wind pressures in ASCE 7-10, minimum wind loads from ASCE 27.1.5 and 28.4.4 as a separate, simultaneous load case, and over-rides of the intensity of minimum pressures for local design codes.

  1. Intensity of Minimum Wind Loads

    For ASCE 2005, a minimum wind load of 10 psf was applied to the walls and the projected roof area. For ASCE 7-10, this has been changed to 16 psf for walls and 8 psf for roofs. Because of the new 0.6 ASD load factor for winds, this amounts to virtually the same wall loads, but a reduction in roof loads by ½.

    Note that gable ends are treated as walls, not roofs, despite the fact they are modelled as part of the roof creation procedure.

  2. Minimum Wind Load Over-ride

    Certain local design codes require a different minimum load, for example New York City requires 20 psf. Therefore, the program now allows you to adjust the intensity of the minimum load for walls and for roofs, with the defaults being 16 psf and 8 psf. These are input in the Site Information dialog box, and are recorded in the Site Information output table.

  3. Minimum Loads as a Separate Load Case

    As Commentary C27.4.7 states that minimum loads are to be applied “as a separate load case in addition to the normal load cases..”, the program now generates minimum loads simultaneously with either Directional (All Heights) or Envelope (Low-rise) loads and calculates shearline forces separately for those loads.

    1. Previous Procedure

      Previously, a checkbox in the Load Generation input allowed you to generate minimum loads. The operation was different for All Heights vs. Low-rise loads; for All Heights, the program would selectively apply the minimum load to building elements that it determined were not loaded to the minimum for the all-heights procedure; for Low-rise, the program would generate minimum loads on the structure but not generate low-rise loads. You had to make separate runs and compare your results manually.

      The input in the Load Generation box has been eliminated, along with associated message box warnings.

    2. New Procedure

      The program always creates loads due to the minimum pressure on walls and the projected roof area. It then distributes loads to the shearlines using each set of loads, and determines the heaviest loading to use for shearwall design. That is, the program compares the shearline forces derived from minimum loads to all four low-rise cases in a particular direction, or two the Case 1 and Case 2 all heights loads, and chooses the critical force for design.

    3. Plan View

      A choice “Minimum” has been added to the Show… menu under “Wind Load Case”, enabling you to see the loads and shearline forces created using Minimum loads. An equivalent checkbox has been added to the Loads and Forces settings.

    4. Load Input View

      In the Load Input View, the word Min appears in the load list for generated minimum loads. It is not possible to designate a force that you enter manually as minimum.

    5. Load and Force Output

      In all the tables that currently have a column for load case word, the word Min has been added for minimum loads, with an explanation in the legend below:

Wind Shear Loads

Hold-down Design

Drag Strut Forces

The note regarding the previous minimum load procedure has been removed from the Wind Shear Loads table.

  1. Shear Design Output

    The note that previously appeared saying that you must run minimum loads separately from normal load cases and compare has been removed.

  2. Log File

    Minimum loads do not appear in the load generation section of the log file, as the log file output shows intermediate data used to arrive at the pressures used to generate loads, and minimum loads specify the pressure without the intermediate data.

    In the torsional analysis section of the log file for rigid diaphragms, the case showing the calculations for minimum loads is shown by e.g. E->W and N->S WIND DESIGN (MINIMUM LOADS)

  3. Files from Previous Versions

    The program detects whether a project from a previous version of the program includes minimum loads, and then prompts you with a recommendation to delete the loads and regenerate.

See Also

Wind Load Generation

Wind Method Nomenclature

Importance Factor I

Simultaneous Case 1 and Case 2 Load Cases

Envelope (Low-rise) Load Model

Low Rise Loads on Hip Roof

Over-rides of Case 2 Eccentricity and Load Percentage

Limitation of Case 2 Loads to Three Stories or More

Wind Pressure Constant

Component and Cladding (C&C) Loads

Wind Load Generation Inputs – Miscellaneous Changes

Wind Load Generation in Design Results Summary – Miscellaneous Changes

Wind Load Generation in Log File – Miscellaneous Changes