All loads entered in Sizer are not to include the importance factor in the load magnitude. Sizer automatically applies this factor when load combinations are constructed, according to the user-input Importance Category and the following design code clauses:
NBC
Section 4.1.2.1 .3) and Table 4.1.2.1 p 4-3 – Define Importance Categories
NBC Structural Commentaries
CSA O86-14
Section 5.2.3.2, Table 5.2.3.2.
Input
The means of entering importance factors is described in Load Settings and Options.
Output
The importance factors for all load types that exist on the member are output at the head of the load combination list in the analysis results as follows:
LC# Ultimate Limit States Serviceability Limit States Pattern
---- --------------------- --------------------------- -------
Importance factors also included:
Snow: 1.15 Snow: 0.9
Wind: 1.15 Wind: 0.75
Earthquake: 1.3
Where individual load combinations are output in the Design Check results or Analysis Diagrams, the importance factor appears in brackets within the load combination:
LC #15 = 1.0D+1.0Ds+0.5L+1.0Ls+(1.15)0.25S+(1.3)1.0E
In both cases, the live load factor is output only for low-hazard buildings, otherwise it is 1.0.
Serviceability Importance Factor for Earthquake Loads
The design codes do not provide a serviceability factor for earthquake loads, and no earthquake combinations are generated for serviceability design. Sizer does not perform deflection design for earthquake load combinations.
Part 9 Snow Loads
For structures meeting the requirements of Part 9 of the NBC, many users design using Part 4 but with snow loads specified using Part 9, In this case, the importance factor is 1.0 for serviceability (deflection) rather than the 0.9 Part 4 importance factor shown in O86 Table 5.2.3.2. For this reason there is an Importance category called Normal, Part 9 snow. When this is selected, the factors are the same as for the Normal importance category, except that for snow loads are selected the serviceability limit state (SLS) factor is rather than 0.9