The unit shear resistance governed by sheathing-to-framing connection strength is given in O86 11.6.2.2.(a) as
vrs = Vrs / Ls = f vd JD ns Jus Js Jhd
Safety Factor f
f = 0.8.
Unit shear strength vd
Unit lateral shear strength vd = Nu/s, where Nu is the factored unit lateral nail resistance from O86 12.9.3.1. Note that the modification K-factors are included in the factored nail resistance Nu so do not appear directly in the equation for Vrs
JD Factor for Diaphragm and Shear Wall Construction
As per 12.9.3.1 1 factor is always set to 1.3 for shear wall design.
Number of Shear Planes nS
As mid-panel shear walls are not to be included in Shearwalls, the value of ns is always 1.
Unblocked Factor Jus
Refer to Unblocked Factor Jus and Unblocked Wall Design
Spacing Factor Js
As per 11.5.1, the fastener spacing factor Js is applied to each side of a wall with wood structural panel sheathing and lumber framing. This factor is
Js = 1 - [( 150 - s ) / 150]4.2
Shearwalls applies this factor as is to other framing materials such as structural composite lumber ( LVL, LSL, etc.). If you are using these framing materials, it is your responsibility to check the proprietary product literature for the adjustment factor for the material, as recommended in the Note to 11.5.1 and make the necessary adjustments to shearwall capacity manually.
Hold-down Effect Factor Jhd
Refer to Hold-down Effect Factor Jhd.