Previous Topic

Next Topic

Book Contents

Book Index

Axial Compression

Using O86 6.5.6.2 for sawn lumber, 7.5.8.5 for glulam, 8.4.7.2 for CLT, and 15.3.3.5.2 for SCL, SIzer determines resistance to axial compression loads in columns, wall studs, and wall panels with an equation of the form

Pr = f Fc AKCKZc

The slenderness factor and size factor are evaluated for buckling in each orthogonal direction and the worst case of the resulting resistance Pr is compared to the axial force on the member for each load combination.

The program shows both b- and d- direction resistance and factors in the Design Check results.

Refer to Axial Design for CLT Wall Panels for more a more detailed explanation of CLT compression design.

Built-up Columns

Sizer implements O86 6.5.5.4 for built-up beam compressive design. An input allows you to specify whether the member is nailed, bolted, connected by split rings, or "not adequately connected". A factor corresponding to each method is applied to the compressive strength in the direction of buckling along the member depth. This direction is also evaluated with the Kzc calculations based on single-ply with, with no factor applied. If it is not adequately connected, only the single ply calculation is done. The factors are also evaluated in the direction along the member width b, and the worst of the 3 cases is used for design.

See Also

Design Criteria

Bending Moment Design

Shear Design

Bearing Design

Axial Tension

Combined Lateral Bending and Axial Load

Deflection Design

Vibration-controlled Span

Fire Design