The Stability Factor CP for CLT Wall panels is given in NDS Commentary C3.7.1.4, Equations C3.7.1-1 to -4. This equation is also in the CLT Handbook, Chapter 8, Section 4.1.4.1, Equation 16.
where
le is the effective length between lateral supports, which is Ke l for wall panels, l being the unsupported distance, which in most cases is the panel height L, and (EI)app-min is described in NDS 10.4.1 - CLT Stiffness .
The column buckling resistance PcE is also required for for CLT combined axial and bending design.
Continuously Supported Panels
For the unusual case that the CLT panel would be continuously supported, placing the equation for (EI)app-min’ in the expression for PcE and setting l = 0 yields PcE = (GA)eff Emin / κ E . This results in a CP less than 1.0 despite the continuous support. However, the derivation of Euler buckling factor involves some simplifying assumptions that break down at very small unsupported lengths, so that this result is unrealistic. For continuously supported members, we assume that CP = 1.0.