Adjustment factors applicable to CLT Design are given in NDS Table 10.3.1:
Table 10.3.1 also includes the following factors which have no effect on CLT floor, roof, or wall panel design in Sizer:
NDS 10.3.3 says that information on moisture factors is supplied by manufacturers, and as most manufacturers do not recommend wet service, the program assumes dry moisture conditions and a CM = 1.0.
CLT floor and roof panels are continuously laterally supported on both edges, as the one-foot design width is supported by the rest of the panel. CLT wall panels are also continuously supported. Lateral support spacing is considered on the depth d face for wall panels for the CP factor for axial compression, but this is not the direction for lateral support for out-of-plane bending design. The one-foot design width on the b face is continuously supported.